Part Number Hot Search : 
00105 SP233 PA1912 1N5394G U74LV TT375N CY7C15 FC113
Product Description
Full Text Search
 

To Download DS2500D5S Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  diesel generator set ds02500d5s 380v C 11 kv/50 hz/standby/fuel consumption optimized mtu 16v4000g63/water charge air cooling product highlights optional equipment and ? nishing shown. standard may vary. // bene? ts - low fuel consumtion - optimized system integration ability - high reliability - high availability of power - long maintenance intervals // mtu onsite energy is a single-source supplier // support - global product support offered // standards - engine-generator set is designed and manufactured in facilities certi? ed to standards iso 2008:9001 and iso 2004:14001 - generator set complies to iso 8528 - generator meets nema mg1, bs5000, iso, din en and iec standards - nfpa 110 // power rating - system ratings: 2200 kva - 2600 kva - accepts rated load in one step per nfpa 110 - generator set complies to g3 according to iso 8528-5 - generator set exceeds load steps according to iso 8528-5 // performance assurance certi? cation (pac) - engine-generator set tested to iso 8528-5 for transient response - 85% load factor - veri? ed product design, quality and performance integrity - all engine systems are prototype and factory tested // complete range of accessories available - control panel - circuit breaker/power distribution - fuel system - fuel connections with shut-off valve mounted to base frame - starting/charging system - exhaust system - mechanical and electrical driven radiators - medium voltage alternators // emissions - fuel consumption optimized // certi? cations - ce certi? cation option
2 // / / ds02500d5s / 50 hz / 380v - 11kv application data ? // engine manufacturer mtu model 16v4000g63 type 4-cycle arrangement 16v displacement: l 76.3 bore: mm 170 stroke: mm 210 compression ratio 16.4 rated speed: rpm 1500 engine governor adec (ecu 7) max power: kwm 2185 air cleaner dry // fuel system maximum fuel lift: m 5 total fuel ? ow: l/min 20 // fuel consumption ? l/hr g/kwh at 100% of power rating: 513.3 195 at 75% of power rating: 381.1 193 at 50% of power rating: 260.6 198 // liquid capacity (lubrication) total oil system capacity: l 300 engine jacket water capacity: l 175 system coolant capacity: l 50 // combustion air requirements combustion air volume: m 3 /s 2.6 max. air intake restriction: mbar 50 // cooling/radiator system coolant ? ow rate (ht circuit): m 3 /h 68.5 coolant ? ow rate (lt circuit): m 3 /h 30 heat rejection to coolant: kw 800 heat radiated to charge air cooling: kw 410 heat radiated to ambient: kw 90 fan power for mech. radiator (40c): kwm 44 // exhaust system exhaust gas temp. (after turbocharger): c 490 exhaust gas volume: m 3 /s 6.6 maximum allowable back pressure: mbar 85 minimum allowable back pressure: mbar 30 ? all data refers only to the engine and is based on iso standard conditions (25c and 100m above sea level). ? values referenced are in accordance with iso 3046-1. conversion calculated with fuel density of 0.83 g/ml. all fuel consumption values refer to rated engine power.
3 // / / ds02500d5s / 50 hz / 380v - 11kv // engine 4-cycle standard single stage air ? lter oil drain extension & shut-off valve closed crankcase ventilation governor-electronic isochronous common rail fuel injection fuel consumption optimized engine represents standard features ? represents optional features standard and optional features // system ratings (kw/kva) generator model voltage fuel consumption optimized 40c/400m without radiator with mechanical radiator with electr. driven radiator kwel* kva** amps kwel* kva** amps kwel* kva* amps marathon 744rsl7092 380 v 1880 2350 3570 1880 2350 3570 1840 2300 3494 (low voltage 400 v 1920 2400 3464 1920 2400 3464 1880 2350 3392 marathon standard) 415 v 1800 2250 3130 1800 2250 3130 1760 2200 3061 marathon 1020fdl7093 380 v 1880 2350 3570 1880 2350 3570 1840 2300 3494 (low voltage 400 v 1920 2400 3464 1920 2400 3464 1880 2350 3392 marathon oversized) 415 v 1800 2250 3130 1800 2250 3130 1760 2200 3061 marathon 1020fdl7093 380 v 2080 2600 3950 2040 2550 3874 2040 2550 3974 (low voltage marathon 400 v 2072 2590 3738 2000 2500 3608 2000 2500 3608 de-rating optimized) 415 v 2040 2550 3548 2000 2500 3478 2000 2500 3478 marathon 1020fdh7099 11 kv 2040 2550 134 2000 2500 131 2000 2500 131 (medium volt. marathon) * cos phi = 1,0 ** cos phi = 0,8 // generator nema mg1, bs5000, iso, din en and iec standards self-ventilated superior voltage waveform solid state, volts-per-hertz regulator no load to full load regulation 0,25% voltage regulation no load to full load brushless alternator with brushless pilot exciter 4 pole, rotating ? eld sustained short circuit current of up to 250% of the rated current for up to 10 seconds (marathon generator) ? sustained short circuit current of up to 300% of the rated current for up to 10 seconds (leroy somer generator) marathon low voltage generator ? leroy somer generator (please contact your local mtu onsite energy distribution partner for system ratings) ? oversized generator ? medium voltage generator
4 // / / ds02500d5s / 50 hz / 380v - 11kv represents standard features ? represents optional features standard and optional features, continuation // control panel pre-wired control cabinet for easy application of customized controller (v1+) ? island operation (v2) ? automatic mains failure operation with ats (v3a) ? automatic mains failure operation incl. control of generator and mains breaker (v3b) ? island parallel operation of multiple gensets (v4) ? automatic mains failure operation with short (< 10s) mains parallel overlap synchronization (v5) ? mains parallel operation of a single genset (v6) ? mains parallel operation of multiple gensets (v7) ? basler controller ? deif controller complete system metering digital metering engine parameters generator protection functions engine protection sae j1939 engine ecu communications parametrization software multilingual capability multiple programmable contact inputs multiple contact outputs event recording ip 54 front panel rating with integrated gasket ? different expansion modules ? remote annunciator ? daytank control ? generator winding temperature monitoring ? generator bearing temperature monitoring ? differential protection with multi-finction protection relay ? modbus rtu-tcp gateway // cooling system jacket water pump thermostat(s) water charge air cooling ? mechanical radiator ? electrical driven front-end cooler ? jacket water heater // circuit breaker/power distribution ? 3-pole circuit breaker ? 4-pole circuit breaker ? manual-actuated circuit breaker ? electrical-actuated circuit breaker ? stand-alone solution in seperate switch box // fuel system flexible fuel connectors mounted to base frame ? fuel filter with water separator ? switchable fuel filter with water separator ? seperate fuel cooler ? fuel cooler integrated into cooling equipment
5 // / / ds02500d5s / 50 hz / 380v - 11kv // exhaust system ? exhaust bellows with connection flange ? exhaust silencer with 10 db(a) sound attenuation ? exhaust silencer with 30 db(a) sound attenuation ? exhaust silencer with 40 db(a) sound attenuation ? y-connection-pipe represents standard features ? represents optional features standard and optional features, continuation // starting/charging system 24v starter ? starter batteries ? battery rack & cables ? battery charger // mounting system welded base frame resilient engine and generator mounting modular base frame design
6 // / / ds02500d5s / 50 hz / 380v - 11kv subject to change. | 3237591 | edition 01/14 | enc 2014-01. mtu onsite energy a rolls-royce power systems brand www.mtuonsiteenergy.com weights and dimensions sound data // consult your local mtu onsite energy distributor for sound data. emissions data // consult your local mtu onsite energy distributor for emissions data. rating definitions and conditions // standby ratings apply to installations served by a reliable utility source. the standby rating is applicable to varying loads f or the duration of a power outage. no overload capability for this rating. ratings are in accordance with iso 8528-1, iso-3046-1, bs 5514, as 2789, and din 6271. average load factor: < 85%. operating hours/year: max. 500. // deration factor: altitude: consult your local mtu onsite energy power generation distributor for altitude derations. temperature: consult your local mtu onsite energy power generation distributor for temperature derations. rated power is available up to 40c and 400m above sea level. system dimensions (l x w x h) weight (dry/less tank) open power unit (opu) 5090 x 1836 x 2330 mm 12893 kg materials and speci? cations subject to change without notice. weights and dimensions are based on open power units and are estimates only. consult the factory for accurate weights and dimen sions for your speci? c engine-generator set. drawing above for illustration purposes only, based an standard open power 400 volt engine-generator set. lengths may vary with other voltages. do not use for installation design. see website for unit speci? c template drawings.


▲Up To Search▲   

 
Price & Availability of DS2500D5S

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X